| DN | NPS | L | ØD | ØD1 | ØD2 | b | Z-d |
|---|---|---|---|---|---|---|---|
| 40 | 1½” | 180 | 150 | 110 | 84 | 18 | 4-19 |
| 50 | 2″ | 200 | 165 | 125 | 99 | 20 | 4-19 |
| 65 | 2½” | 240 | 185 | 145 | 118 | 20 | 4-19 |
| 80 | 3″ | 260 | 200 | 160 | 132 | 22 | 8-19 |
| 100 | 4″ | 300 | 220 | 180 | 156 | 24 | 8-19 |
| 125 | 5″ | 350 | 250 | 210 | 184 | 26 | 8-19 |
| 150 | 6″ | 400 | 285 | 240 | 211 | 26 | 8-23 |
| 200 | 8″ | 500 | 340 | 295 | 266 | 30 | 12-23 |
| 250 | 10″ | 600 | 405 | 355 | 319 | 32 | 12-28 |
| 300 | 12″ | 700 | 460 | 410 | 370 | 32 | 12-28 |
| 350 | 14″ | 800 | 520 | 470 | 429 | 36 | 16-28 |
| 400 | 16″ | 900 | 580 | 525 | 480 | 38 | 16-31 |
The Swing Check Valve with Counterweight is designed to automatically control reverse flow in piping systems. Forward-moving fluid causes the disc to swing away from the seat, creating an open flow passage. When the flow slows or begins to reverse, the disc returns toward the seat and closes the valve.
An external lever and counterweight assist the closing movement of the disc and allow the closing characteristics to be better suited to the pipeline operating conditions. The valve operates automatically and does not require a separate powered actuator.
Its ductile iron construction, flanged connection and durable internal components make it particularly suitable for water distribution, pumping stations and industrial utility services.
Municipal Water Networks • Pumping Stations • Water Treatment Plants • Power & Utility Systems • Industrial Water Lines • Petroleum Facilities • Irrigation Networks • Fire-Water Systems • General Pipeline Backflow Protection
Technical Note: Material grades, coating thickness, dimensions and applicable standards should be confirmed against the final manufacturer’s approved datasheet before specifying the valve for a particular project.
| Component | Material |
|---|---|
| Body | Ductile Iron |
| Disc | Ductile Iron |
| Seat | Brass / Stainless Steel / Rubber |
| Lever | Ductile Iron |
| Counterweight | Ductile Iron |
| Parameter | Standard |
|---|---|
| Face-to-Face Dimensions | DIN 3202 |
| Flanged Connection | DIN EN 1092-2 |
| Pressure Testing | DIN EN 12266 |